CONSTRUCTION
Conductor | : | Each conductor shall consist of a solid round/stranded wire(s) of annealed high conductivity copper, smoothly drawn, nominally circular in section , uniform in quality and resistance and free from defects. |
Insulation | : | Insulation shall be of PVC Compound conforming to requirements of Type-A compound of IS 5831:1984. Insulation color shall be as per customer specification. |
Sheath | : | The sheath shall be of PVC Compound conforming to requirements of Type- ST1 as per IS 5831:1984. |
Core Formation | : | The insulated cores shall be laid up together with suitable lay. The outer most layer shall have right hand lay and the successive layers shall be laid with opposite lay. A polyester tape of suitable thickness shall be helically applied normally in cables with double steel tape with suitable overlap. |
FEATURES
- Availability of conductor sizes ranging from 1.13 mm to 2.80 mm diameter. Cable size ranging from 2 core to 100 cores with 1.0 Sqmm to 50 Sqmm.
- Suitable for use on AC systems (Earthed or unearthed) for rated voltage upto 1100 volts
- Suitable for use on DC systems for rated voltage upto 1500 volts
Nominal Cross Sectional Area | No. of Wires in Conductors | Nom. Dia of Wire | Max. Resistance at 20°C | Nom. Thickness of Insualtion | ||
Single Core | Multi Core | Single Core | Multi Core | |||
Sqmm | No(s) | mm | Ω/Km | Ω/Km | mm | mm |
1.0 | 1 | 1.13 | 17.689 | 18.04 | 1.5 | 0.8 |
1.5 | 1 | 1.4 | 11.54 | 11.77 | 1.5 | 0.8 |
2.5 | 1 | 1.80 | 6.978 | 7.118 | 1.5 | 0.9 |
2.5 | 3 | 1.06 | 6.843 | 6.980 | 1.5 | 0.9 |
4 | 1 | 2.24 | 4.506 | 4.596 | 1.5 | 1.0 |
4 | 7 | 0.85 | 4.591 | 4.683 | 1.5 | 1.0 |
6 | 1 | 2.8 | 2.884 | 2.942 | 1.5 | 1.0 |
10 | 7 | 1.4 | 1.660 | 1.693 | 1.5 | 1.0 |
16 | 7 | 1.70 | 1.124 | 1.149 | 1.5 | 1.0 |
25 | 7 | 2.24 | 0.6484 | 0.6614 | 1.5 | 1.2 |
35 | 7 | 2.50 | 0.5205 | 0.5309 | 1.5 | 1.2 |
50 | 19 | 1.8 | 0.3706 | 0.3780 | 1.5 | 1.4 |
Note:
- The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360
- In view of continuous improvements in our design and process, specifications given here in are subject change without notice.