AEW

Cable Structure

ConductorMaterial – Copper According to VDE 0295 class 1 or 2 (IEC 60228,IS 8130)
InsulationPVC Type A of IS:5831
Inner SheathPVC
ArmouringSingle layer of GS round wire or Flat Strips
Outer SheathPVC TYPE ST-1 OF IS : 5831

PVC Armoured Cables
Power cables for energy supply are installed outdoors, in underground, in water, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks, where mechanical damages are no

Standard length cable packing:
Coils 100, 200, 300, 500, 1000 m. in wooden reels

Operating Temp.-20°c to max.+90°C
Nominal voltage1100 V
Test voltage3000 V
Insulation resistanceMin. 10 MΩ x km
Min. bending radiusSingle core :15 X Overall diameter
  Multi core :12 X Overall diameter
Flame propagationFlame retardant test as per IEC 60332-1
Single core2 Core3 Core4 Core5 Core
Black or Yellow/GreenBlue and Brown or Yellow-Green and BlackBrown, Black, Grey or Yellow/Green, Blue, BrownBlue, Brown, Black, Grey or Yellow/Green, Brown, Black, GreyBlue, Brown, Black, Grey, Black or Yellow/Green, Blue, Brown, Black, Grey
AEW 1.1 kV 3 CORE COPPER CONDUCTOR PVC INSULATED , INNER SHEATHED ARMOURED PVC SHEATHED CABLES (IS : 1554 PART 1 ) CABLE CODE : YWY/YFY
SIZE (MM2)INSULATION PVC THICKNESS IN MM (NOM.)INNER SHEATH PVC THICKNESS IN MM (MIN.)ARMOUR SIZE IN MM (G.I)OUTER SHEATH PVC THICKNESS IN MM (MIN.)APPROX OUTER SHEATH O/D IN MMAPPROX WEIGHT OF CABLE (KGS./KM)MAX.DC CONDUCTOR RESISTANCE at 20° C (Ohm/Km)Current Ratings (Amp.)
MAIN COREHALF COREWHDirect In GroundIn Air
3.5C X 250.900.700.304.00.801.4022.7014240.727120125
3.5C X 350.900.700.304.00.801.4024.5017480.524145155
3.5C X 501.000.900.304.00.801.5628.5023910.387170190
3.5C X 701.100.900.404.00.801.5032.1531080.268210235
3.5C X 951.101.000.404.00.801.5636.1040820.193250290
3.5C X 1201.201.100.504.00.801.7240.5051350.153285330
3.5C X 1501.401.100.504.00.801.8844.1061370.124315375
3.5C X 1851.601.100.604.00.802.0449.1575420.0991355435
3.5C X 2401.701.200.704.00.802.2054.6094330.0754410510
3.5C X 3001.801.400.804.00.802.3660.40115670.0601460590
3.5C X 4002.001.600.804.00.802.5268.10149830.0470520670
3.5C X 5002.201.701.004.00.802.8476.10186990.0366580750

AEW 1.1 kV 3 CORE COPPER CONDUCTOR PVC INSULATED , INNER SHEATHED ARMOURED PVC SHEATHED CABLES (IS : 1554 PART 1 )
CABLE CODE : YWY/YFY

SIZE (MM2)

INSULATION PVC THICKNESS IN MM (NOM.)

INNER SHEATH PVC THICKNESS IN MM (MIN.)

ARMOUR SIZE IN MM (G.I)

OUTER SHEATH PVC THICKNESS IN MM (MIN.)

APPROX OUTER SHEATH O/D IN MM

APPROX WEIGHT OF CABLE (KGS./KM)

MAX.DC CONDUCTOR RESISTANCE at 20° C (Ohm/Km)

Current Ratings (Amp.)
WHDirect
In
Ground
In Air
3 C X 1.50.800.301.401.2413.2037712.102117
3 C X 2.50.900.301.401.2414.404547.412724
3 C X 41.000.301.401.2416.506034.613630
3 C X 61.000.301.401.4017.907203.084539
3 C X 101.000.304.00.801.4018.858281.836052
3 C X 161.000.304.00.801.4021.0010921.157766
3 C X 251.200.304.00.801.4021.6012700.7279990
3 C X 351.200.304.00.801.4023.5016020.524120110
3 C X 501.400.304.00.801.4026.8521410.387145135
3 C X 701.400.404.00.801.5629.9527620.268175165
3 C X 951.600.404.00.801.5633.9036360.193210200
3 C X 1201.600.404.00.801.5636.5544380.153240230
3 C X 1501.800.504.00.801.7240.6054480.124270265
3 C X 1852.000.504.00.801.8844.5065550.0991300305
3 C X 2402.200.604.00.802.0449.6082200.0754345355
3 C X 3002.400.604.00.802.2054.70101120.0601385400
3 C X 4002.600.704.00.802.3661.60132080.0470425