Conductor : Annealed Tinned Copper (Class 5) IEC/EN 60228
Insulation : Halogen Free Cross Linked Polyolefin (XLPO) (Natural Colour) BS EN 50618:2014
Sheath : Halogen Free Cross Linked Polyolefin (XLPO) (Black Colour) BS EN 50618:2014
Fire Properties :
Flame Retardant EN 60332-1-2
Halogen Free HCL content < 0.5 % IEC 60754-1
Low Toxic Gases (Toxicity Index < 2%) CEI 20-37 / 4-0
Low Smoke Emission (Transmitted > 60%) EN 61034-2

These cables are designed for connecting photovoltaic power supply and can be used in flexible & fixed installations for indoor / outdoor usage with high mechanical strength under extreme weather conditions.

  • In Continuous exposure of UV radiations the cable has excellent weathering properties.
  • Halogen free hence in case of fire, it does not emit toxic material and generates only low smoke.
  • Fire Retardant.
  • Very Flexible – Easy Installation as it is made of Stranded Conductors.
  • Withstands high temperatures.
  • Customized designs available – Chemical or EBM Crosslinking.
  • Life time over 30 years under harsh environment.
Size in mm2Nom.Ins. Thickness in mmNom.Sheath. Thickness in mmAppx. Overall Dia in mmTinned Copper D.C Conductor Resistance ohm./kmCurrent Carrying Capicity at 60 ‘C in Air (Amps.)Permissible Short Circuit Current (Isc) 5 sec. (kA)
1.50.500.504.1013.700300.19
2.50.500.504.508.210410.32
40.500.505.205.090550.5
60.500.505.703.390700.76
100.500.506.901.950981.26
160.500.508.001.2401322
250.901.0011.000.7951763.15
350.901.1012.300.5652184.41
500.901.2014.500.3932766.3
701.001.3016.700.2773478.82
951.101.5019.100.21041612
1201.201.6021.200.16448815.1
1501.401.7024.000.13256618.9
1851.601.9026.800.10864423.3
2401.702.1029.900.081777530.4