Products Range
Menu



CONSTRUCTION
Conductor | : | Finely stranded bare flexible copper conductor |
Insulation | : | PVC |
Sheath | : | PVC |
Core Colours | : | 3core : Red, Yellow, Black, |
: | 4core: Red, Yellow, Black, Green |
For continuous use in deep well to supply power to submersible motors for the depth upto 500 mtrs.
Conductor Size (AWG) | Nos and Dia. of wire (Nos. x mm) | Core Dia. (mm) | Nominal Sheath Thickness (mm) | Cable Overall Dimension (mm) |
14 | 41 x 0.254 | 3.60 | 1.15 | 13.30 x 6.20 |
12 | 65 x 0.254 | 4.30 | 1.15 | 15.60 x 7.00 |
10 | 105 x 0.254 | 5.10 | 1.15 | 17.70 x 7.40 |
8 | 168 x 0.254 | 6.30 | 1.40 | 22.30 x 9.30 |
6 | 226 x 0.254 | 7.60 | 1.40 | 26.30 x 10.80 |
4 | 420 x 0.254 | 9.90 | 2.00 | 32.30 x 13.10 |
2 | 665 x 0.254 | 11.10 | 2.00 | 35.90 x 14.30 |
1 | 817 x 0.254 | 13.60 | 2.20 | 45.50 x 18.30 |
1/0 | 1045 x 0.254 | 13.60 | 2.20 | 45.50 x 18.30 |
2/0 | 1330 x 0.254 | 15.60 | 2.20 | 51.00 x 21.00 |
3/0 | 1672 x 0.254 | 18.00 | 2.40 | 61.00 x 23.50 |
4/0 | 2116 x 0.254 | 19.80 | 2.65 | 65.00 x 25.20 |
250 MCM | 2503 x 0.254 | 20.60 | 2.80 | 68.00 x 28.00 |
Conductor Size (AWG) | Nos and Dia. of wire (Nos. x mm) | Ground Conductor Size (AWG) | Core Dia. (mm) | Nominal Sheath Thickness (mm) | Cable Overall Dimension (mm) |
14 | 41 x 0.254 | 14 | 3.85 | 1.15 | 18.00 x 6.50 |
12 | 65 x 0.254 | 12 | 4.50 | 1.15 | 21.00 x 7.60 |
10 | 105 x 0.254 | 10 | 5.30 | 1.15 | 24.30 x 7.90 |
8 | 168 x 0.254 | 10 | 6.50 | 1.40 | 29.70 x 9.90 |
6 | 266 x 0.254 | 8 | 8.00 | 2.00 | 36.00 x 11.80 |
4 | 420 x 0.254 | 8 | 10.10 | 2.00 | 45.10 x 14.70 |
2 | 665 x 0.254 | 6 | 11.30 | 2.20 | 50.10 x 16.20 |
1 | 817 x 0.254 | 6 | 13.60 | 2.20 | 58.10 x 19.00 |
1/0 | 1045 x 0.254 | 6 | 13.60 | 2.20 | 58.10 x 19.00 |
2/0 | 1330 x 0.254 | 4 | 15.60 | 2.20 | 66.50 x 21.50 |
3/0 | 1672 x 0.254 | 2 | 18.00 | 2.65 | 77.30 x 23.50 |
4/0 | 2116 x 0.254 | 2 | 19.80 | 3.85 | 87.00 x 27.80 |
- Excellent resistant to moisture, abrasion, greace,oil.
- Excellent mechanical & electrical properties.
- Generally Conforming to : CENELEC HD 21, IEC 60227, BS 6500, DIN VDE 0281, IS 694.
- Temperature range -15°C to +70°C
Note:
- The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360
- In view of continuous improvements in our design and process, specifications given here in are subject change without notice.