AEW

STRUCTURE

ConductorMultiple-wire, round copper conductor class 2, DIN VDE 0281, IEC 60228
InsulationPVC insulation compound TI-1
ColourGreen/Yellow, Blue, Black, Brown, Grey, Orange, Pink, Red, Violet, White, Green, Yellow or other colours
Flame propagationFlame retardant test as per IEC 60332-1

H05V-K, H07V-K:
Fixed installation in conduits and under plaster, for appliance wiring and distribution stations

Standard length cable packing:
Coils 100 and 200 m in carton boxes, reels

Operating Temp-20°C to max.+80°C
Nominal voltageHO5V-R : 300/500 V
HO7V-R : 450/750 V
Test voltageHO5V-R : 2000 V
HO7V-R : 2500 V
Insulation resistanceMin. 10 MΩ x km
Min. bending radius4 x cable diameter
  • High current carrying capacity
  • Excellent resistant to moisture, abrasion, grace, oil
  • Fine copper wires
  • Longer Flex Life
  • Excellent mechanical & electrical properties
  • harmonized acc. to European standards
  • Steam and boiling water resistant
  • Tested by SGS, EIL, RITES, NPC, INTERTEK
Size in mm2Nos/ dia. (Nom.)Insulation Thickness in mm ( nom.)Outer Dia in mm (Appx.)Max. C.R in ohm/km Copper
0.516/0.2000.602.1039.00
0.7524/0.2000.602.2026.00
132/0.2000.602.7019.50
Size in mm2Nos/ dia. (Nom.)Insulation Thickness in mm ( nom.)Outer Dia in mm (Appx.)Max. C.R in ohm/km Copper
1.530/0.2500.703.2513.30
2.550/0.2500.803.807.98
456/0.3000.804.504.95
684/0.3000.805.253.30
10140/0.3001.006.501.91
16224/0.3001.008.001.21
25350/0.3001.2010.100.780
35490/0.3001.2011.300.554
50703/0.3001.4013.500.386
70988/0.3001.4015.300.272
951349/0.3001.6018.000.206
120608/0.5001.6019.800.161
150760/0.5001.8022.300.129
185943/0.5002.0023.900.106
2401225/0.5002.2026.800.0801

Note:

  • The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360 or UL83